CONFIGURING DELTA ANALOG MODULE (DVP-O6XA-S) WITH DELTA PLC (DVP-12SA2)
1.WIRING DIAGRAM
- NOTE: External 24vdc needs to connect with module
- Check and confirm the module number and whether it will communicate with PLC in manual
PLC Programming:
- Create a new project.
- Select SA2 model PLC
- · Select the Auxiliary Setup for Extension
- Select the place of the AI module from the PLC don’t consider the DI and DO module
- · Select the DVP-06AX-S model AI module and go to setup
- · Click #2Mode setting
- · Select Write register (Generate TO Instruction)
- · Condition as LD M1000 for always On condition
- · Select (-20mA - +20mA) as choice of programmer
- · Click Preview ->Add to List instruction get appears on Instruction List
- Select and configure each channel to read from the analog module
· Click the
- · Click the check box of #CH Input Average -> Read Register (Generate FROM Instruction)
- · Condition as LD M1000 for always On condition
- · Give alternate register number in Register for Storing Data
- · Click ok to add the corresponding API as figured in the below picture
1. Here K0-constant 0 is mentioned in the module position
2. K1 as #1Input mode
3. H6DB as module number
4. K1 Number of Data
- Now I need floating datatype so enabling M1163 bit for floating data type
- Scaling has to be done as per the double data type scaling with floating F constant
- First, all raw values need to convert to float type, and then using DSCLP scaling has to be done as follows
- Here maximum engineering values are mentioned
- Here minimum engineering values are mentioned
- Here max sensor scale value is mentioned
- Here min sensor scale value is mentioned
- Resolution varies based on the modules we have chosen.
*Floats accommodate 32-bit so we are using DMOV D100, D102